— ENERGY MONITORING AND REPORTING EAp2 Required
能源监测与报告 EAp2 必须满足
To support energy management practices and facilitate identification of ongoing opportunities for energy and greenhouse gas (GHG) emissions savings by tracking and reporting building energy use and demand.
通过追踪与报告建筑能源使用及需求,支持能源管理实践,并促进持续识别节能与温室气体(GHG)减排机会。
Achievement Pathways Points Existing Buildings N/A Energy Monitoring AND Report Energy Data Comply with the following requirements: Energy Monitoring
能源监测 以及 报告能源数据 遵守以下要求:
• Have permanently installed energy meters or submeters that measure total building energy consumption for each energy source (electricity, on-site renewable electricity, natural gas, chilled water, steam, hot water, fuel oil, propane, etc.). Utility-owned meters capable of aggregating total project energy use by energy source are acceptable. Delivered fuels, such as propane, oil, diesel, or wood, must be tracked and reported by delivery date and amount if they are not metered or submetered.
能源监测
• Calibrate meters within the manufacturer’s recommended interval if the project owner or management organization has oversight over the meter.
• 安装永久安装的能源计量表或子表,测量每种能源(电力、现场可再生电力、天然气、冷冻水、蒸汽、热水、燃油、丙烷等)的建筑总能耗。能够按能源汇总项目总能源使用的公用事业自有表也可接受。若丙烷、燃油、柴油或木材等交付燃料未装表或子表,须按交付日期与数量追踪并报告。
• Tenant meters may be excluded for up to 10% of the gross building area. When excluded, the associated area shall also be excluded to determine the intensity of energy use or GHG emissions. AND Report Energy Data Report monthly energy use data by energy source for the 12-month reporting period. Following certification, commit to ongoing reporting of monthly energy data on an annual basis.
• 若项目业主或管理组织对计量表拥有监督权,须按制造商建议的间隔进行校准。
• 租户表最多可排除总建筑面积的 10%。排除时,相关面积也须一并排除,以计算能源使用或 GHG 排放强度。
以及 报告能源数据 报告 12 个月报告期内按能源分类的月度能源使用数据。认证后,承诺每年持续报告月度能源数据。