EQp2 — FUNDAMENTAL AIR QUALITY
基础空气质量
REQUIRED 先决条件
适用项目类型:New Construction 新建建筑
影响领域(Impact Area Alignment):
— Decarbonization 脱碳
✓ Quality of Life 生活质量
✓ Ecological Conservation and Restoration 生态保护与修复
INTENT 意图
To design for above-average indoor air quality to support occupant health and well-being.
设计超出平均水平的室内空气质量以支持使用者的健康和福祉。
REQUIREMENTS 要求
| Achievement Pathways 达成路径 | Points 分值 |
New Construction and Core and Shell 新建建筑与核心外壳项目 | N/A 必需 |
Investigate Regional and Local Air Quality 调查区域和当地空气质量 | — |
| AND 且 | — |
Ventilation and Filtration Design 通风与过滤设计 | — |
| AND 且 | — |
Entryway System Design 入口系统设计 | — |
Investigate Regional and Local Air Quality 调查区域和当地空气质量
Investigate outdoor air quality in accordance with ASHRAE Standard 62.1-2022, Sections 4.1–4.3.
依据ASHRAE Standard 62.1-2022第4.1–4.3节调查室外空气质量。
AND — Ventilation and Filtration Design 通风与过滤设计
Meet the requirements of ASHRAE Standard 62.1-2022, Sections 5 and 6. Use the ventilation rate procedure, the IAQ procedure, the natural ventilation procedure, or a combination thereof.
满足ASHRAE Standard 62.1-2022第5和第6节的要求。使用通风速率法、IAQ法、自然通风法或它们的组合。
Where the ventilation rate procedure or IAQ procedure are used, comply with the following additional provisions:
如使用通风速率法或IAQ法,需满足以下附加规定:
Filtration 过滤要求
Each central HVAC system that supplies outdoor air and/or recirculated air to regularly occupied spaces must meet one of the following:
每个向常规使用空间供应室外空气和/或循环空气的中央HVAC系统必须满足以下之一:
- Minimum efficiency reporting value (MERV) of 13, in accordance with ASHRAE Standard 52.2–2017;
根据ASHRAE Standard 52.2–2017,最低效率报告值(MERV)达到13;
- OR Equivalent filtration media class of ePM1 50%, as defined by ISO 16890-2016, Particulate Air Filters for General Ventilation — Determination of the Filtration Performance;
或根据ISO 16890-2016定义的等效过滤介质等级ePM1 50%;
- OR In-room air-cleaning systems;
或室内空气净化系统;
Systems tested for effectiveness and safety per ASHRAE Standard 241-2023, Section 7.4 (and Normative Appendix A). If treating for particles and gases, use systems tested for effectiveness per ASHRAE 62.1-2022, Addendum N. If treating for infectious aerosols, use systems tested for effectiveness per ASHRAE Standard 241-2023, Section 7.
系统需根据ASHRAE Standard 241-2023第7.4节(及规范性附录A)测试有效性和安全性。如处理颗粒物和气体,使用根据ASHRAE 62.1-2022附录N测试有效性的系统。如处理传染性气溶胶,使用根据ASHRAE Standard 241-2023第7节测试有效性的系统。
Outdoor Air Measurement 室外空气测量
Provide outdoor airflow measurement devices for all mechanical ventilation systems with outdoor air intake flow greater than 1,000 cfm (472 L/s).
为所有室外空气进风量大于1,000 cfm(472 L/s)的机械通风系统提供室外空气流量测量装置。
Healthcare 医疗建筑专项要求
- For healthcare spaces, meet the requirements of Sections 6–10 of ASHRAE Standard 170-2021.
医疗空间须满足ASHRAE Standard 170-2021第6-10节的要求。
Residential 住宅建筑专项要求
For residential spaces, follow the additional dwelling unit provisions below.
住宅空间须遵循以下额外的居住单元规定。
Dwelling Unit Provisions 居住单元规定
If the project building contains residential units, each dwelling unit must meet all the following requirements:
如项目建筑包含住宅单元,每个居住单元须满足以下所有要求:
- Mechanical ventilation / 机械通风:Design and install a dwelling-unit mechanical ventilation system that complies with ASHRAE 62.2-2022, Sections 4, 6.6, and 6.7. Supply and balanced mechanical ventilation systems must be designed and constructed to provide ventilation air directly from the outdoors. Mechanical ventilation systems are not required when the project meets the exception detailed in ASHRAE 62.2-2022, Section 4.1.1.
设计并安装符合ASHRAE 62.2-2022第4、6.6和6.7节的居住单元机械通风系统。当项目满足ASHRAE 62.2-2022第4.1.1节详细列出的例外情况时,不需要机械通风系统。
- Kitchen and bathroom exhaust / 厨房和浴室排风:Design and install local mechanical exhaust systems in each kitchen and bathroom, including half baths, that comply with ASHRAE 62.2-2022, Sections 5 and 7. Exhaust air to the outdoors. Do not route exhaust ducts to terminate in attics or interstitial spaces. Recirculating range hoods or recirculating over-the-range microwaves do not satisfy the kitchen exhaust requirements. For exhaust hood systems capable of exhausting in excess of 400 cubic feet per minute (188 liters per second), provide makeup air at a rate approximately equal to the exhaust air rate. Makeup air systems must have a means of closure and be automatically controlled to start and operate simultaneously with the exhaust system. Use ENERGY STAR labeled bathroom exhaust fans in all bathrooms (including half baths) or performance equivalent for projects outside the U.S. An HRV heat recovery ventilator (HRV) or ERV energy recovery ventilator (ERV) may be used to exhaust single or multiple bathrooms if it has an efficacy level meeting the ENERGY STAR Technical Specifications for Residential Heat-Recovery Ventilators and Energy-Recovery Ventilators (H/ERVs), version 2.3 as certified by the Home Ventilating Institute.
每个厨房和浴室(包括半卫)设计并安装局部机械排风系统,符合ASHRAE 62.2-2022第5和7节。排风应直接排至室外。不得将排风管道引至阁楼或夹层空间。循环式抽油烟机或循环式微波炉不能满足厨房排风要求。美国以外的项目须使用性能相当的浴室排风扇。可使用热回收通风器(HRV)或能量回收通风器(ERV)为单个或多个浴室排风。
- Unvented combustion appliances / 无通风燃烧设备:Unvented combustion appliances (ovens and ranges excluded) are not allowed.
不允许使用无通风燃烧设备(烤箱和炉灶除外)。
- CO monitor / CO 监测器:A carbon monoxide (CO) monitor must be installed on each floor of each dwelling unit, hard-wired with a battery backup. CO monitors are required in all types of units, regardless of the type of equipment installed in the unit.
每个居住单元的每一层须安装一氧化碳(CO)监测器,采用硬接线并配备电池备用。所有类型的单元均需要CO监测器,无论单元内安装何种类型的设备。
- Indoor fireplaces and woodstoves / 室内壁炉和燃木炉:Any indoor fireplaces and woodstoves must have solid glass enclosures or doors that seal when closed. Any indoor fireplaces and woodstoves that are not closed combustion or power-vented must pass a backdraft potential test to ensure that depressurization of the combustion appliance zone is less than 5 Pa.
任何室内壁炉和燃木炉必须具有实心玻璃围护或在关闭时可密封的门。非封闭式燃烧或动力通风的室内壁炉和燃木炉必须通过回风潜力测试,确保燃烧设备区域的负压小于5 Pa。
- Space- and water-heating equipment / 空间及热水加热设备:Space- and water-heating equipment that involves combustion must be designed and installed with closed combustion (i.e., sealed supply air and exhaust ducting) or with power-vented exhaust or located in a detached utility building or open-air facility.
涉及燃烧的空间和热水加热设备必须设计并安装为封闭式燃烧(即密封的供气和排气管道),或采用动力通风排气,或位于独立的辅助建筑或露天设施中。
AND — Entryway System Design 入口系统设计
Install permanent entryway systems to capture dirt and particulates entering the building at primary exterior entrances. There is no length requirement for entryway systems.
在主要外部入口处安装永久性入口系统以捕捉进入建筑的污垢和颗粒物。对入口系统长度没有要求。
版权声明:LEED® 为 USGBC/GBCI 注册商标,原始内容版权归 USGBC 所有。
| 本页面为官方资料的
中文摘要与要点提炼,并附英文原文对照。
| 仅供学员学习参考使用,不可替代官方 Reference Guide。
| 如需正式项目申报,请登录
usgbc.org 获取完整官方文件。