— FUNDAMENTAL AIR QUALITY EQp2 Required
Quality of Life · 生活质量 EQp2 必须满足
To design for above-average indoor air quality that supports occupant health and well-being.通过设计达到优于一般水平的室内空气质量,以支撑使用者的健康与福祉。
Three linked requirements: (1) investigate regional and local outdoor air quality per ASHRAE 62.1-2022 Sections 4.1-4.3, considering seasonal and climate-change variations; (2) meet ASHRAE 62.1-2022 Sections 5-6 via VRP, IAQP, or natural ventilation, with central HVAC serving regularly occupied spaces providing at least MERV 13 (or ePM1 50%, or in-room air cleaning per ASHRAE 241), plus outdoor-airflow measurement for systems >1,000 cfm, and healthcare/residential addenda; and (3) install permanent entryway systems at all primary exterior entrances (no length requirement). Healthcare follows ASHRAE 170-2021; residential dwelling units add mechanical ventilation, kitchen/bath exhaust, CO monitors, and combustion-safety provisions.三项相互关联的要求:(1)按 ASHRAE 62.1-2022 第 4.1–4.3 节调查区域与地方室外空气质量,考量季节与气候变化;(2)通过 VRP、IAQP 或自然通风满足 ASHRAE 62.1-2022 第 5–6 节,向经常使用空间送风的中央 HVAC 至少达 MERV 13(或 ePM1 50%,或符合 ASHRAE 241 的室内空气净化),且对风量大于 1000 cfm 的系统设室外风量监测,并遵循医疗与住宅补充规定;(3)在所有主要室外入口设置永久性入口除尘系统(无长度要求)。医疗项目遵循 ASHRAE 170-2021;住宅单元另需机械通风、厨卫排风、一氧化碳报警器及燃烧安全条款。
Investigate outdoor air quality locally and regionally, including seasonal pollen, wildfire PM2.5, and ozone patterns, informed by the Climate Resilience Assessment.Provide at least MERV 13 / ePM1 50% filtration (or compliant in-room air cleaning) on central HVAC serving regularly occupied spaces; airflow monitoring required above 1,000 cfm.Meet ASHRAE 62.1-2022 via VRP, IAQP, or natural ventilation; IAQP adds post-completion testing and occupant survey.Install permanent entryway systems (grates, grilles, slotted, or rollout mats) at all primary exterior entrances to capture dirt and particulates.Residential and healthcare projects have additional ventilation, exhaust, CO-monitoring, and combustion-appliance safety requirements. 调查地方与区域室外空气质量,包括季节性花粉、野火 PM2.5 与臭氧,并参考气候韧性评估。向经常使用空间送风的中央 HVAC 提供至少 MERV 13 / ePM1 50% 过滤(或合规室内净化);风量超 1000 cfm 须设室外风量监测。通过 VRP、IAQP 或自然通风满足 ASHRAE 62.1-2022;采用 IAQP 需竣工后做检测与使用者调查。在所有主要室外入口设置永久性入口除尘系统(格栅、槽式或卷垫)以拦截尘土。住宅与医疗项目另有通风、排风、一氧化碳报警及燃烧器具安全等附加要求。