EAc7 — ENHANCED REFRIGERANT MANAGEMENT
增强制冷剂管理

CREDIT New Construction and Core and Shell 1–2分

影响领域:✓ Decarbonization

INTENT 意图

To reduce direct greenhouse gas emissions from refrigerants and to encourage early adoption of buildings that do not use harmful refrigerants to support a just transition of the HVAC&R industry.

减少制冷剂的直接温室气体排放,鼓励尽早采用不使用有害制冷剂的建筑,支持暖通空调行业的公平转型。

REQUIREMENTS 要求

Achievement PathwaysPoints
New Construction and Core and Shell1–2
Option 1. No Refrigerants or Low-Impact Refrigerants
无制冷剂或低影响制冷剂
2
OR 或者
Option 2. Calculation of Refrigerant Impact
制冷剂影响计算
1

OPTION 1 No Refrigerants or Low-Impact Refrigerants (2 points)
无制冷剂或低影响制冷剂(2分)

Do not use refrigerants, OR use only refrigerants (naturally occurring or synthetic) that have an ozone depletion potential (ODP) of zero and a global warming potential (GWP) of less than 10.

不使用制冷剂,或仅使用ODP为零且GWP<10的制冷剂(天然或合成)。

OPTION 2 Calculation of Refrigerant Impact (1 point)
制冷剂影响计算(1分)

Calculate the lifecycle refrigerant GWP for all HVAC&R systems serving the project, and demonstrate that it does not exceed the maximum thresholds in Table 1.

计算所有服务于项目的暖通空调制冷系统的全生命周期制冷剂GWP,并证明不超过表1的最大值。

Table 1. Maximum Lifecycle Refrigerant GWP Allowance
表1. 最大生命周期制冷剂GWP允许值
Climate Zone 气候分区Maximum Refrigerant GWP (kg CO₂e / ton cooling)
最大GWP(kg CO₂当量/冷吨)
0, 1, 22,500
3, 41,750
5, 6, 7, 81,500

Calculation Method 计算方法:

LCGWP = Σ [ (GWPr × (Lr × 寿命 + Mr) × Rc × 全生命周期) ] / Qtotal

where: LCGWP = lifecycle GWP per ton cooling; GWPr = refrigerant GWP; Lr = annual leak rate (2%); Mr = end-of-life loss (10%); Rc = refrigerant charge per system; Qtotal = total cooling capacity in tons.


LEED v5 Reference Guide | Pages 123–125