计算 · 学习 · 标准
Indoor Environmental Quality / 室内环境质量

Ventilation Performance

通风绩效
EQc2 Credit
EN

— VENTILATION PERFORMANCE EQc2 3–5 points

CN

通风绩效 EQc2 3–5 分

Intent / 意图

EN

To provide increased indoor air quality to better protect the health of building occupants.

CN

提升室内空气质量,更好地保护建筑使用者的健康。

Requirements / 要求

EN

Achievement Pathways Points Existing Buildings 3–5 Ventilation Performance 3–5 Ventilation per ANSI/ASHRAE Standard 62.1 Demonstrate that outdoor air ventilation rates of all occupied spaces meet or exceed ASHRAE 62.1-2022 or later based on the measurements reported in EQp1: Verification of Ventilation and Filtration. Alternatively, the rates may meet or exceed the ventilation rate procedure outlined in Section 6.2 of ASHRAE 62.1,7 editions 2016, 2013, 2010, or 2007.If demonstrating exceedance from the referenced standard, increased outdoor air rates shall be provided to 95% of all regularly occupied spaces. Naturally ventilated spaces meet ASHRAE 62.1-2022, “Natural Ventilation Procedure,” or exceed opening sizes or natural ventilation airflow rates of ASHRAE 62.1-2022, “Natural Ventilation Procedure.” If demonstrating exceedance from the referenced standard, increased outdoor air rates (or opening sizes) shall be provided to 95% of all regularly occupied spaces. Points are awarded according to

CN

达标路径:通风绩效(3–5 分)。

EN

Table 1.

CN

依据 ANSI/ASHRAE 62.1 标准的通风 基于 EQp1:通风与过滤验证 中报告的实测数据,证明所有使用空间的室外新风量达到或超过 ASHRAE 62.1-2022 或更新版本的要求;也可达到或超过 ASHRAE 62.1(2016、2013、2010 或 2007 版)第 6.2 节通风率法的要求。若以"超出所引用标准"申报,则须为 95% 的常用使用空间提供提高后的室外新风量。

EN

Table 1. Points for ventilation Ventilation Performance Points Meet referenced standard 3 Exceed referenced standard by 15% 4 Exceed referenced standard by 30% 5 7 ASHRAE, “Ventilation and Acceptable Indoor Air Quality,” ASHRAE 62.1-2022, 2022, accessed March 31, 2025, https://www.ashrae.org/technical-resources/bookstore/standards-62-1-62-2, https://www.ashrae.org/technical-resources/bookstore/standards-62-1-62-2.

CN

自然通风空间须满足 ASHRAE 62.1-2022"自然通风法",或超过该方法规定的开口尺寸或自然通风风量。若以"超出所引用标准"申报,则须为 95% 的常用使用空间提供提高后的室外新风量(或开口尺寸)。

EN

 

CN

得分依据表 1。

EN

 

CN

表 1. 通风得分(通风绩效 | 得分):达到所引用标准 | 3;超出所引用标准 15% | 4;超出所引用标准 30% | 5。

EN

 

CN

注:所引用标准为 ASHRAE 62.1-2022《通风与可接受的室内空气质量》。

^ Indoor Air Quality Performance ← 工具箱 ← O+M 首页 Occupant Experience Performance v v