— GREENHOUSE GAS EMISSIONS REDUCTION PERFORMANCE EAc1 1–12 points
温室气体减排绩效 EAc1 1–12 分
To reduce environmental and economic harm associated with greenhouse gas (GHG) emissions from building energy use that disproportionately impacts frontline communities.
减少与建筑能源使用相关的温室气体(GHG)排放所造成的环境与经济危害,这些危害对前沿社区的影响尤为严重。
Achievement Pathways Points Existing Buildings 1–12
选项 1. 现场燃烧温室气体排放(1–5 分)路径 1. ENERGY STAR NextGen™ 目标(1–5 分)或 路径 2. 历史基线目标(1–5 分)或 路径 3. 现场燃烧排放强度目标(1–5 分)
Option 1. Greenhouse Gas Emissions from On-Site Combustion 1–5
以及/或 选项 2. 可再生能源(1–4 分)
Path 1. ENERGY STAR NextGen™ Target 1–5 OR
以及/或 选项 3. 建筑能源使用的总温室气体排放(1–3 分)路径 1. 相对同类建筑的绩效(1–3 分)或 路径 2. 相对历史基线的绩效(1–3 分)
Path 2. Historical Baseline Target 1–5 OR
选项 1. 现场燃烧温室气体排放(1–5 分) 基于 EAp3:最低能源绩效 中报告的项目能源数据,证明现场燃烧排放低于现场燃烧排放目标的百分比改善。得分依据表 1。既不使用现场燃烧(应急支持系统除外,每年使用少于 200 小时),也不使用区域供热的项目自动获得 5 分。使用任意适用路径确定现场燃烧排放目标。
Path 3. On-Site Combustion Emissions Intensity Target 1–5
AND/OR
Option 2. Renewable Energy 1–4
AND/OR
Option 3. Total Greenhouse Gas Emissions from Building Energy Use 1–3
Path 1. Performance Relative to Similar Buildings 1–3 OR
Path 2. Performance Relative to Historical Baseline 1–3
Option 1. Greenhouse Gas Emissions from On-Site Combustion (1– 5 points) Demonstrate a percentage improvement in on-site combustion emissions below the on-site combustion emissions target based on the project energy data reported in EAp3: Minimum Energy Performance. Points are awarded according to
Table 1. Projects that use neither on-site combustion, except for emergency support systems (used less than 200 hours per year), nor district heating automatically achieve 5 points. Determine the on-site combustion emissions target using any applicable path. PATH 1. ENERGY STAR NEXTGEN TARGET (1–5 POINTS) Determine the target by multiplying the ENERGY STAR NextGen Direct (GHGi) target by 1.4. Reference the ENERGY STAR Portfolio Manager Technical Reference for ENERGY STAR NextGen and direct GHGi targets.5 OR PATH 2. HISTORICAL BASELINE TARGET (1–5 POINTS) Calculate the total GHG emissions from on-site combustion for the current 12-month reporting period compared to a historical baseline from a 12-month reporting period with similar occupancy occurring within eight years before the end of the 12-month reporting period. Historical data may be normalized against the reporting period for weather or operational variables, such as occupancy or production throughput. OR PATH 3. ON-SITE COMBUSTION EMISSIONS INTENSITY TARGET (1–5 POINTS) Available Path 3 is available only to projects using EAp3: Minimum Energy Performance,
Option 2. Determine on-site combustion emissions intensity targets for the project’s building type(s) and climate zone according to Appendix II.
Table 1. Points for Percentage Reduction Below On-Site Combustion Emissions Targets Points Reduction Below On-Site Combustion Emissions Targets (%) 1 20% 2 40% 3 60% 4 80% 5 100%
AND/OR
Option 2. Renewable Energy (1– 4 points) Supply or procure renewable energy meeting the renewable energy criteria below. Points are awarded according to
Table 2. 5 ENERGY STAR, “ENERGY START NextGen™ Direct GHGi Targets,” 2024, https://www.energystar.gov/buildings/tools-and-resources/technical-reference-energy-star-nextgen-ghgi-targets. Points documented for Tier 1, Tier 2, and/or Tier 3 renewable energy may be added together up to a maximum of 4 points.
Table 2. Points for Renewable Energy Procurement Points Tier 1 Tier 2 Tier 3 Minimum Rated Capacity* OR Annual Electric Energy Use (%) Annual Electric Energy Use (%) Annual Electric Energy Use (%) 1 A × 1 W/sq. ft. (A × 10.8 W/sq. m.) OR 5% 20% 50% 2 A × 2 W/sq. ft. (A × 22.5 W/sq. m.) OR 10% 40% 100% 3 20% 60% 4 30% 80% *A = Sum of gross floor area of all floors up to the three largest floors. RENEWABLE ENERGY CLASSIFICATIONS
Tier 1. On-Site Renewable Energy Generation or Social Impact Project The renewable generation equipment may be located:
Tier 2. New off-site Renewable Electricity Off-site renewable electricity produced by new generation asset(s):
Tier 3. Off-site Renewable Energy
AND/OR
Option 3. Total Greenhouse Gas Emissions from Building Energy Use (1 –3 points) Demonstrate a percentage improvement in project GHG emissions from building energy use below the total GHG emissions target. Points are awarded according to
Table 3. Calculate the project GHG emissions for the 12-month reporting period using the project energy consumption for each energy source and the project GHG emissions factors for each energy source. Report project electricity use with a GHG emissions factor of zero when the electricity is supplied or offset by Tier 1; on-site renewable energy generation or social impact project, and/or Tier 2; new off-site renewable electricity, documented in
Option 2. Renewable Energy. Calculate GHG emissions targets using one of the following:either Path 1 or
Path 2. PATH 1. PERFORMANCE RELATIVE TO SIMILAR BUILDINGS (1–3 POINTS) GHG emissions targets shall be calculated based on the site energy use intensity targets for fuel and electricity for the project’s building type and climate zone in Appendix II. For all project locations, multiply these targets by the published U.S. Environmental Protection Agency national CO 2 equivalent (CO2eq) emissions factors for natural gas and electricity from the most recently published year. OR PATH 2. PERFORMANCE RELATIVE TO HISTORICAL BASELINE (1–3 POINTS) Calculate the historical baseline target derived using the site energy data for each building energy source from a 12-month reporting period with similar occupancy occurring within eight years before the end of the 12-month reporting period, and the project GHG emissions factor for each energy source during the historical reference period. Historical data may be normalized against the reporting period for weather or operational variables, such as occupancy or production throughput. If the project generated on-site renewable energy or procured off-site renewable energy during the historical reporting period, treat this identically to nonrenewable energy for the purposes of calculating the GHG emissions target.
Table 3. Points for Percentage Reduction Below GHG Emissions Target Points Reduction (%) 1 15% 2 30% 3 60% For all options District Energy
• On the project site
• On the campus on which a project is located
• On the site of an social impact project, provided that the renewable power system is provided, installed, and commissioned at no cost to the social impact entity; that the ownership of the renewable power system is transferred to the social impact entity; and that the rights to the power provided be given to the social impact entity
• Off-site renewable electricity produced by new generation asset(s) initially contracted no more than five years after the asset’s commercial operations date
• Off-site renewable electricity that is Green-e® Energy certified or equivalent
• Renewable fuels that are Green-e Energy certified or equivalent RENEWABLE ENERGY CRITERIA Contract Length Project shall demonstrate a minimum of a three-year contractual commitment that begins no later than the project’s reporting period start date. Contract length shall be three years or prorated across three years for shorter contract lengths. Environmental Attributes Ownership All environmental attributes (Energy Attribute Certificates [EACs]) or Renewable Energy Certificates [RECs]) associated with renewable energy generation must be retired on behalf of the LEED project for the renewable energy procurement to contribute to credit achievement. Vintage EACs/RECs credited to the project must be generated no earlier than 18 months before the LEED project’s initial submission date. Location Tier 2 and Tier 3 renewable assets must be in the same country or region where the LEED project is located.
• Projects with district energy must comply with the requirements of this credit at the district facility or see additional guidance for interpretation of credit requirements.