— FUNDAMENTAL REFRIGERANT MANAGEMENT EAp5 New Construction and Core and Shell: Required (no points)
Decarbonization · 脱碳 EAp5 New Construction and Core and Shell: Required (no 分)
To reduce greenhouse gas emissions from refrigerants by accelerating the phaseout of high-global-warming-potential (GWP) refrigerants and by reducing refrigerant leakage.通过加速淘汰高全球变暖潜值(GWP)制冷剂并减少制冷剂泄漏,降低制冷剂产生的温室气体排放。
Option 1 (No Refrigerants): use no refrigerant equipment (devices under 0.5 lb are exempt). Option 2 (Refrigerants) requires: a complete refrigerant inventory (type, GWP, charge, total GWP) for all equipment in scope plus existing owner equipment; no HCFC refrigerants in new equipment; evaluation of alternatives during design for any refrigerant with GWP > 700; and a leak check and repair prior to substantial completion (with vacuum/pressure testing for field-assembled joints before charging). Renovations must properly recover, recycle, reclaim, or destroy removed refrigerants per EPA/EC regulations.方案 1(无制冷剂):不使用含制冷剂设备(低于 0.5 磅的设备豁免)。方案 2(含制冷剂)须:对范围内所有设备及业主既有设备建立完整制冷剂清单(种类、GWP、充注量、总 GWP);新设备不得采用 HCFC 制冷剂;对 GWP > 700 的制冷剂在设计阶段评估替代方案;在实质性完工前进行检漏与修复(现场拼接管路在充注前须做真空/压力测试)。改造项目须按 EPA/欧盟法规对拆除的制冷剂进行回收、再利用、再处理或销毁。
GWP is assessed per IPCC AR4 or later; common high-GWP examples include R-410A (2088) and R-134a (1430), while natural refrigerants (R-290, R-744 CO2, R-717 ammonia) are near zero.Develop a list of GWP ≤ 700 alternatives early; if >700 is impractical, consider reclaimed refrigerant.Equipment under 0.5 lb (e.g., residential refrigerators) is excluded from the inventory.Field-assembled piping needs vacuum and pressure testing to limit leakage.Core and Shell inventories base-building and owner equipment, excluding tenant equipment not in scope. GWP 按 IPCC 第四次评估报告或更新版评估;常见高 GWP 如 R-410A(2088)、R-134a(1430),天然制冷剂(R-290、R-744 CO2、R-717 氨)接近零。尽早制定 GWP ≤ 700 的替代清单;若 >700 不可行,可考虑再生制冷剂。低于 0.5 磅的设备(如住宅冰箱)不计入清单。现场拼接管路须做真空与压力测试以控制泄漏。核心与外壳仅统计基础建筑及业主设备,不含范围外的租户设备。