— ENHANCED AIR QUALITY EQc1 1–2 points
增强空气质量 EQc1 1–2 分
To design for increased indoor air quality (IAQ) to better protect the health of building occupants.
设计高于平均水平的室内空气质量(IAQ),更好地保护建筑使用者的健康。
Achievement Pathways Points Commercial Interiors 1–2
达标路径 分值 商业室内 1–2 选项 1 增加通风 1–2 或 选项 2 增强室内空气质量设计 1 或 选项 3 通风与过滤验证 1
Option 1. Increased Ventilation 1-2
设计项目超出 ASHRAE 标准 62.1-2022 第 6 节要求。若采用通风量程序满足 EQp2(基础空气质量),则使用选项 1 或选项 2;若采用室内空气质量程序(IAQP),则使用选项 2。
OR
选项 1. 增加通风(1–2 分)
Option 2. Enhanced Indoor Air Quality Design 1
将呼吸区新风通风率较 EQp2 确定的最小率高至少 15%(1 分)或 30%(2 分)。增加的新风率应提供给 95% 的经常有人空间。
OR
或 选项 2. 增强室内空气质量设计(1 分)
Option 3. Verification of Ventilation and Filtration 1 Design the project to exceed the requirements of ASHRAE 62.1-2022, Section 6. If using the ventilation rate procedure to comply with EQp2: Fundamental Air Quality, use Option 1 or Option 2; if using the indoor air quality procedure (IAQP), use
除 ASHRAE 62.1-2022 表 6-5、6-6 的设计化合物与设计限值外,采用下表所列较低设计限值设计并验证增强 IAQ。
Option 2.
表 1. 增强 IAQ 设计的附加设计限值
Option 1. Increased Ventilation ( 1–2 points) Increase breathing zone outdoor air ventilation rates by at least 15% above the minimum rates (for 1 point, or 30% for 2 points) as determined in EQp2: Fundamental Air Quality. Increased outdoor air rates should be provided to 95% of all regularly occupied spaces.
设计化合物或 PM2.5 增强 IAQP 设计限值
OR
PM2.5 10 µg/m³
Option 2. Enhanced Indoor Air Quality Design (1 point) In addition to the design compounds and design limits outlined in ASHRAE 62.1-2022, Tables 6-5 and 6-6, design and verify enhanced IAQ using the lower design limits listed below in
甲醛 20 µg/m³
Table 1.
臭氧 10 ppb
Table 1. Additional Design Limits for Enhanced IAQ Design Design Compound or PM2.5 Enhanced IAQP Design Limit* PM2.5 10 µg/m3 Formaldehyde 20 µg/m³ Ozone 10 ppb Note: ppb = parts per billion.
注:ppb = 十亿分之一(parts per billion)。
OR
或 选项 3. 通风与过滤验证(1 分)
Option 3. Verification of Ventilation and Filtration (1 point) For spaces receiving mechanical ventilation from base building systems, measure the total quantity of outdoor air delivered to the project and verify the results are within 10% of the rates reported in EQp2: Fundamental Air Quality and outlined in the current facilities requirements and operations and maintenance plan. Measurements shall quantify the amount of outdoor air for each base building air-handling unit serving the project and account for worst-case conditions. NOTE: This path is only applicable for tenant improvements to a previously occupied space and is not applicable for initial build-out.
对接收 base building 系统机械通风的空间,测量输送到项目的新风总量,验证结果在 EQp2 报告率的 10% 以内,并符合当前设施要求与运行维护计划。测量须量化服务项目的每个 base building 空气处理机组的新风量,并考虑最不利工况。
注:此路径仅适用于既有空间的租户改造,不适用于首次装修。