— FUNDAMENTAL REFRIGERANT MANAGEMENT EAp5 Required
基础制冷剂管理 EAp5 必须满足
To reduce GHG emissions from refrigerants by accelerating the phaseout of refrigerants with high global warming potential (GWP) and by reducing refrigerant leakage.
通过加速淘汰高全球变暖潜值(GWP)制冷剂并减少泄漏,降低制冷剂产生的温室气体排放。
Achievement Pathways Points Commercial Interiors N/A
达标路径:N/A
Option 1. No Refrigerants
选项 1. 不使用制冷剂 项目不使用任何制冷剂。
OR
或 选项 2. 使用制冷剂 项目范围内安装、更换或改造的含制冷剂设备须满足:
Option 2. Refrigerants
注:制冷剂清单可以租户为单位,也可以整栋建筑为单位,只要包含租户系统即可。
Option 1. No Refrigerants Do not use refrigerants in the project.
OR
Option 2. Refrigerants Meet the following requirements for refrigerant-containing equipment installed, replaced, or altered in the project scope of work:
• Complete refrigerant inventory: Complete an inventory of the refrigerant-containing equipment installed within the project scope of work and any existing equipment under control of the tenant. The inventory shall include the refrigerant type, GWP, amounts of refrigerants contained in each, and the total GWP of all refrigerants.
• Do not use hydrochlorofluorocarbon (HCFC) refrigerants in new equipment.
• Evaluate available alternatives during the design process for any refrigerants with GWP > 700.
• Leak check and repair. Prior to substantial completion, check both new and existing refrigerant-containing equipment for refrigerant leaks and repair all leaks identified. For systems with field-assembled joints, perform a leak check, vacuum check, and pressure check prior to charging with refrigerant. NOTE: The refrigerant inventory may be documented for the tenant or for the entire building, provided that these include tenant systems.