EAc1 Electrification
EAc1 电气化

EAc1 — 1–5 Points | 1–5分

EAc1 — 1–5 Points | 1–5分

Impact Area Alignment: Decarbonization

影响领域对齐:脱碳

Intent | 意图

To encourage buildings to be designed so that they do not depend on burning fuel on-site, which leads to better indoor and outdoor air quality and to low-carbon operations as the grid decarbonizes.

鼓励建筑设计不依赖现场燃烧燃料,从而获得更好的室内外空气质量,并随着电网脱碳实现低碳运营。

Requirements | 要求

OptionPoints
Option 1. No On-Site Combustion (Base + Tenant)5
Option 2. No On-Site Combustion Except at Low Temperatures1–5
Option 3. No On-Site Combustion, Limited Scope1–3
Option 4. Base Building Documentation + Tenant Compliance5

Option 1: No On-Site Combustion (5 points)

Design and operate with no on-site combustion except emergency support systems. Combined weighted average COP ≥ 1.8 (initial) or ≥ 1.2 (alterations).

设计和运营时不进行现场燃烧(紧急支持系统除外)。综合加权平均COP ≥ 1.8(初始建设)或 ≥ 1.2(改造)。

Option 2 Paths | 选项2路径

PathPointsDescription | 说明
Path 1. Space Heating2空间供暖无现场燃烧(除低温外)
Path 2. SWH1生活热水加热无现场燃烧(除低温外)
Path 3. Cooking and Process Loads1–2烹饪和其他过程负荷无现场燃烧

NOTE: "Low temperatures" refers to outside air dry-bulb below 20°F (−6.5°C).

注:"低温"指室外空气干球温度低于20°F(−6.5°C)。