— FUNDAMENTAL AIR QUALITY EQp2 Required

CN

基础空气质量 EQp2 必须满足

Intent / 意图

EN

To design for above-average indoor air quality (IAQ) to support occupant health and well-being.

CN

设计高于平均水平的室内空气质量(IAQ),支持使用者的健康与福祉。

Requirements / 要求

EN

Achievement Pathways Points Commercial Interiors N/A Investigate Regional and Local Air Quality AND Ventilation and Filtration Design AND Entryway System Designs Comply with the following requirements: Investigate Regional and Local Air Quality Investigate outdoor air quality in accordance with ASHRAE Standard 62.1-2022, Sections 4.1– 4.3. AND Ventilation and Filtration Design Meet the requirements of ASHRAE Standard 62.1-2022, Sections 5 and 6. Use the ventilation rate procedure, the IAQ procedure, the natural ventilation procedure, or a combination thereof. Where the ventilation rate procedure or IAQ procedure are used, comply with the following additional provisions: Filtration Each central HVAC system within the project’s scope of work that supplies outdoor air and/or recirculated air to regularly occupied spaces must meet one of the following:

CN

达标路径 分值 商业室内 不适用 调研区域与本地空气质量 以及 通风与过滤设计 以及 入口系统设计

EN

• Minimum efficiency reporting value of 13, in accordance with ASHRAE Standard 52.2-2017; OR

CN

须符合以下要求:

EN

• Equivalent filtration media class of ePM1 50%, as defined by ISO 16890-2016, “Particulate Air Filters for General Ventilation — Determination of the Filtration Performance.”

CN

调研区域与本地空气质量

EN

• In-room air-cleaning systems. o Use sSystems tested for effectiveness and safety per ASHRAE Standard 241-2023, Section 7.4 and Normative Appendix A. If treating for particles and gases, use systems tested for effectiveness per ASHRAE 62.1-2022, Addendum n. If treating for infectious aerosols, use systems tested for effectiveness per ASHRAE Standard 241-2023, Section 7. Outdoor air measurement Provide outdoor airflow measurement devices for all mechanical ventilation systems in the project scope of work with outdoor air intake flow greater than 1,000 cfm (472 L/s). Healthcare

CN

依据 ASHRAE 标准 62.1-2022 第 4.1–4.3 节调研室外空气质量。

EN

• For healthcare spaces, meet the requirements of Sections 6–10 of ASHRAE Standard 170-2021 as applicable. AND Entryway System Designs Install permanent entryway systems to capture dirt and particulates entering the building at primary exterior entrances within the project scope of work. There is no length requirement for entryway systems.

CN

以及 通风与过滤设计

EN

 

CN

满足 ASHRAE 标准 62.1-2022 第 5、6 节要求。采用通风量程序、IAQ 程序、自然通风程序或其组合。采用通风量程序或 IAQ 程序时,须符合以下附加规定:

EN

 

CN

过滤:项目范围内向经常有人空间供应新风和/或回风的所有集中 HVAC 系统,须满足下列之一:最低效率报告值(MERV)13(依据 ASHRAE 标准 52.2-2017);或等效过滤介质等级 ePM1 50%(依据 ISO 16890-2016《通用通风用空气颗粒过滤器——过滤性能测定》);或室内空气净化系统(依据 ASHRAE 标准 241-2023 第 7.4 节及规范性附录 A 测试有效与安全;处理颗粒与气体用 ASHRAE 62.1-2022 附录 n 测试;处理感染性气溶胶用 ASHRAE 标准 241-2023 第 7 节测试)。

EN

 

CN

新风测量:为项目范围内新风进风量大于 1,000 cfm(472 L/s)的所有机械通风系统提供新风流量测量装置。

EN

 

CN

医疗:医疗空间须适用地满足 ASHRAE 标准 170-2021 第 6–10 节要求。

EN

 

CN

以及 入口系统设计

EN

 

CN

在项目范围的主要外部入口安装永久入口系统以捕获进入建筑的灰尘与颗粒物。入口系统无长度要求。